Quick Answer: As of November 2026, Texas does not have a reliable count of how much water its data centers use. The best estimates come from outside researchers. HARC puts current use at about 25 billion gallons a year and projects 29 billion to 161 billion gallons by 2030. UT Austin projects that data centers’ share of state water use will rise from under 1% today to 3%–9% by 2040. The state’s 2027 water plan contains no data center forecast, and most data centers have not answered the state’s mandatory water-use survey.
In July 2026 the Texas Water Development Board (TWDB) adopted an initial 2027 State Water Plan with a $174 billion list of supply projects and no standalone projection for data centers. State leaders are trying to close the gap with surveys, an audit and an enforcement order, while cities set water terms campus by campus.
How much water do Texas data centers use now?
There is no official statewide total. The two most cited independent estimates come from the Houston Advanced Research Center (HARC) and the University of Texas at Austin.
HARC’s January 21, 2026 report, Thirsty Data and the Lone Star State, estimates that existing Texas data centers use about 25 billion gallons a year, counting both on-site cooling and the water used to generate their electricity. It projects 29 billion to 161 billion gallons a year by 2030, or up to 2.7% of all water used in the state.
UT Austin’s COMPASS consortium at the Bureau of Economic Geology published Water Use Requirements for Data Centers in Texas in May 2026. It estimates that data centers use less than 1% of Texas water today and projects 3% to 9% by 2040. Manufacturing, by comparison, uses about 7%. The researchers counted more than 400 data centers operating or under construction in Texas. Their estimate includes indirect water: the gas, coal and nuclear plants that supply much of Texas’s power use about 5% of the state’s water.
| Estimate | Publisher and date | Current use | Projection |
|---|---|---|---|
| Thirsty Data and the Lone Star State | HARC, Jan. 21, 2026 | About 25 billion gallons per year (cooling plus power generation) | 29–161 billion gallons per year by 2030; up to 2.7% of state use |
| Water Use Requirements for Data Centers in Texas | UT Austin COMPASS / Bureau of Economic Geology, May 2026 | Less than 1% of state water use | 3%–9% of state water use by 2040 |
| Initial 2027 State Water Plan | Texas Water Development Board, adopted July 23, 2026 | Not broken out | No data center projection; methods planned for the 2032 plan |
Source: HARC (January 2026); University of Texas at Austin (May 2026); Texas Water Development Board, as reported by E&E News and Community Impact (July 2026).
The estimates are wide because, as the UT authors note, the result depends on industry growth, cooling choices and power sources. HARC recommended requiring large users to report expected water and electricity use, adding forward-looking forecasts to the State Water Plan, and encouraging “water-lean” technologies such as dry cooling and brackish water reuse.
Why does the 2027 State Water Plan leave data centers out?
When it approved the plan on July 23, 2026, the TWDB denied a petition asking for standalone projections of data center and crypto-mining water demand. Staff said the state was too late in its five-year cycle, and the board said it lacked enough information. TWDB is developing methods to separate that demand for the 2032 plan. The plan drew more than 1,000 public comments, a record, and about 268 dealt with data centers and crypto mining. None of the 16 regional planning groups had asked to change its data center demand projections.
What does the plan say about Texas’s overall water gap?
| Metric (2027 State Water Plan) | Figure |
|---|---|
| Cost of recommended water supply projects | About $174 billion |
| Water demand change, 2030–2080 | Up about 6% |
| Existing supply change, 2030–2080 | Down about 10%, from 15.5 million to nearly 14 million acre-feet |
| Drought-of-record shortage | About 3.6 million acre-feet per year (2030) rising to 5.8 million (2080) |
| Economic damage from severe drought without projects | $91 billion as early as 2030; $177 billion a year by 2080 |
| Projected population, 2080 | More than 52 million (about 31.7 million today) |
Source: Texas Water Development Board, initial 2027 State Water Plan (adopted July 2026), as summarized by Community Impact and Allen Matkins’ Gravel2Gavel blog.
Proposition 4, approved by voters in November 2025, provides $20 billion for water over about two decades, well short of the $174 billion the plan calls for.
Are Texas data centers required to report water use?
Data centers using more than 10 million gallons a year must answer TWDB’s annual water-use survey, which asks for volume, water source and on-site power generation but not cooling technology. Failing to respond is a Class C misdemeanor with a fine of up to $500. TWDB says it is not a regulatory agency, so prosecution is left to local officials.
| Survey year | Data centers surveyed | Response rate |
|---|---|---|
| 2020–2022 | Fewer than 5 | 100% |
| 2023 | 22 | 32% |
| 2024 | 67 | 28% |
| 2025 | 329 (267 newly tracked) | Nearly 30% overall; 22.5% of newly tracked facilities |
Source: Texas Water Development Board data reported by The Texas Tribune (September 2026). At a June 23, 2026 House hearing, TWDB staff cited 341 facilities and a 17% response rate, a figure that later reporting revised upward.
Among respondents, about 98% bought water from public systems. About 89% of reported water came from rivers and reservoirs and about 8% from groundwater. Bitdeer in Rockdale reported more than 300 million gallons a year, the most of any data center in 2025. Google in Midlothian, QTS in Fort Worth and Meta in Fort Worth were also among the largest users. Lawmakers also noted that in counties without a groundwater conservation district, nobody locally regulates a data center’s groundwater pumping.
What has changed in 2025 and 2026?
As of November 2026, Texas has no general requirement for data centers to publicly disclose water use. In 2025 lawmakers directed the Public Utility Commission (PUC) to study the water impacts of power generation and large electricity users. The PUC and TWDB built a questionnaire on water, cooling and power; the Texas Tribune reported it was voluntary, and by June 2026 only 28 companies representing 92 facilities had answered.
- June 10, 2026: Gov. Greg Abbott pledged to seek legislation requiring closed-loop or similar water-efficient cooling for new data centers and annual water and electricity reporting to the PUC.
- August: An ERCOT-led audit of data centers seeking grid connection began collecting water-use, water-source and cooling data, with completion expected by December 2026.
- September 14: Abbott ordered TWDB to use its enforcement authority against non-filers and report on compliance by October 14.
Interim charges direct the Senate Water, Agriculture and Rural Affairs Committee to study high-demand cooling technologies and water affordability, and the House Natural Resources Committee to assess direct and indirect data center water use and water-efficient siting. The Legislature convenes January 12, 2027.
How are specific Texas campuses handling water?
Without state standards, water terms are set project by project, through utility contracts, cooling design and offset programs. Large data centers can use up to 5 million gallons a day, comparable to a small city. Some Texas counties reviewing incentive packages have asked whether a project will use closed-loop or other water-efficient cooling.
Meta in El Paso: a capped potable-water agreement
Meta’s $1.5 billion campus sits on about 1,000 acres in far Northeast El Paso. Under its agreement with El Paso Water, the site may use an average of 750,000 gallons of potable water a day at first, rising to 1.5 million gallons a day after full buildout. At the full permitted level, that is more than the 1.1 million gallons a day Marathon Petroleum’s El Paso refinery averaged from the utility. Meta says its closed-loop liquid cooling will keep actual use far below the cap, targets operations in 2028, and will report the site’s water use in its sustainability report.
San Antonio: recycled water with new fees on the way
The San Antonio Water System (SAWS) runs a 130-mile “purple pipe” recycled water network; Microsoft has used it to cool data centers for years. In November 2026 SAWS reported that data centers use about 0.1% of its potable water and 1.25% of its recycled water. Projects that are in development or in talks would raise those shares to about 0.3% of potable and 12% of recycled water. SAWS has about 10,000 acre-feet of recycled water available for future customers, and pending requests total about 3,000 acre-feet. Recycled water is priced at about 40% of residential drinking-water rates.
SAWS plans a fee for high-volume recycled water users that could start in 2027, is weighing impact fees for new recycled customers (likely 2028 or 2029), and expects a recycled water master plan by the end of 2027.
Microsoft and Rowan in Medina County: air cooling, reuse and offsets
Microsoft says most of its Texas facilities use air-cooled chillers, which use no water for cooling, and most of its water-cooled chillers run on reused water. In February 2026, Rowan announced that its 440-acre Cinco campus near Lytle would use low-water cooling and fund a “250% offset” of its water use through the Edwards Aquifer Conservancy, which helps farmers adopt more efficient irrigation. Rowan has not disclosed volumes.
West Texas: zero surface discharge
In September 2026, Gradiant announced a contract to supply potable water and wastewater treatment for an unnamed hyperscale AI campus in West Texas. The system is designed for zero discharge to surface water. Google has committed to air-cooled, closed-loop cooling at its new data centers.
| Project / utility | Water approach | Disclosed figures |
|---|---|---|
| Meta, El Paso | Closed-loop liquid cooling; El Paso Water agreement | 750,000 gal/day average initially; 1.5 million gal/day at buildout |
| SAWS data center customers | Recycled “purple pipe” water | 1.25% of recycled water now; about 12% projected |
| Microsoft, San Antonio region | Mostly air-cooled chillers; reused water for water-cooled units | No volumes published |
| Rowan Cinco, Medina County | Low-water cooling; Edwards Aquifer conservation offset | 250% offset; 440 acres |
| Unnamed hyperscaler, West Texas | Gradiant integrated water and wastewater treatment | Zero discharge to surface water |
Source: Texas Standard (Meta, 2025); San Antonio Express-News via GovTech (November 2026); Microsoft (October 2025); Rowan Digital Infrastructure (February 2026); Gradiant via Water Online (September 2026).
What does this mean for developers and local governments?
Access to recycled or brackish water is becoming a siting advantage; SAWS says its recycled system leaves San Antonio better positioned for data center growth. Cooling design is under closer review from the state, counties and utilities. Reporting is shifting toward enforcement through the TWDB order, the ERCOT audit and proposed 2027 legislation. Local rules are tightening too: San Antonio now requires a special use permit for new data centers, and San Marcos has barred them within city limits.
Frequently Asked Questions
How much water could Texas data centers use by 2030?
HARC estimates 29 billion to 161 billion gallons a year by 2030, up from about 25 billion today. The high end would be up to 2.7% of statewide water use.
Does the Texas State Water Plan include data centers?
No. The initial 2027 plan, adopted July 23, 2026, has no standalone data center projection. TWDB is developing methods for the 2032 plan.
Do data centers have to report water use in Texas?
Yes, on TWDB’s annual water-use survey, if they use more than 10 million gallons a year. Failing to respond is a Class C misdemeanor. Response rates have stayed around or below 30%.
Where do Texas data centers get their water?
Mostly from public water systems. Among TWDB survey respondents, about 89% of the water came from surface sources and about 8% from groundwater.
Which cooling methods use less water?
Air-cooled chillers and closed-loop liquid systems, which Microsoft, Meta and Google describe using, consume less water than evaporative cooling.
Sources and Further Reading
- Texas Data Center Boom Could Consume Up to 161 Billion Gallons of Water Annually by 2030 — Houston Advanced Research Center
- Data Centers Are Growing in Texas, But Big Questions Remain About Water Use — The University of Texas at Austin
- Texas Data Center Water Supply Report — Texas Standard
- Texas Green-Lights Water Plan Lacking Data Center Forecasts — E&E News
- Texas Includes Minimal Data Center Info in State Water Plan, Citing Limited Data — Community Impact
- Data Center Growth Brings Water Use into Sharper Focus in Texas (Update) — Allen Matkins Gravel2Gavel / JD Supra
- Most Data Centers Won’t Share Data About Water Use with Texas Lawmakers — Texas Public Radio
- Texas Data Centers PUC Water Survey — The Texas Tribune
- Gov. Greg Abbott Orders Texas Water Agency to Penalize Data Centers That Don’t Report Their Water Usage — The Texas Tribune / Route Fifty
- Texas Lawmakers Are Still Trying to Figure Out How Much Water Data Centers Actually Use — KERA / High Plains Public Radio
- Meta to Build $1.5 Billion Data Center in Northeast El Paso — Texas Standard
- San Antonio Water Contemplates Changes for Data Centers — San Antonio Express-News / GovTech
- SAWS Water Sources: Desal and Data Centers — Axios San Antonio
- Microsoft Datacenters in Texas — Microsoft
- Local Investment Drives 250% Water Offset at Cinco — Rowan Digital Infrastructure
- Gradiant Secures Major Water Contract for Hyperscaler AI Data Center Campus in West Texas — Water Online
- Reservoirs Dwindle in South Texas — NASA Earth Observatory